Preliminary claim reportclaimsdesk · Report date 20 October 2026
Fictional example. All companies, persons, figures and documents in this report are invented. It shows what a claimsdesk report looks like. Names appear as placeholders such as [COMPANY_1], exactly as in a real report made from anonymised documents.

Water damage from a sprinkler pipe failure in a logistics warehouse

Report type: claims summary with coverage check · Based on 7 documents (31 pages) · Currency EUR

Claimed412,600
Documented53,100
Questioned2,100
Open or no document357,400

Summary

In the night of 14 September 2026 a coupling in the sprinkler system of a warehouse operated by [COMPANY_1] failed. Water ran into aisles C to F and damaged stored goods, the floor coating and packaging material [D1 p.1] [D2 p.1]. The contractor names internal corrosion of a coupling installed in 2009 as the cause [D3 p.2].

Chronology

Date and timeEventSource
14 Sep 2026, 02:14Sprinkler alarm in section 3 recorded in the alarm log.D3 p.1
14 Sep 2026, 06:40Warehouse manager [PERSON_1] finds water in aisles C to F.D1 p.1
14 Sep 2026, 07:30 / 07:55Main valve closed. The two documents give different times (see check points).D1 p.1 · D3 p.1
15 Sep 2026First notice of loss sent to [INSURER_1].D1 p.1
18 Sep 2026Site visit by loss adjuster [COMPANY_3]; corrosion at the failed coupling noted and photographed.D2 p.2–3
22 Sep 2026Contractor report: coupling failed due to internal corrosion; quote for repair.D3 p.2–3
25 Sep – 3 Oct 2026Drying and cleaning of the affected area.D4 p.1
6 Oct 2026Invoice for drying and cleaning.D4 p.1–2
9 Oct 2026Stock damage list submitted (612 items).D5 p.1–5
10 – 14 Oct 2026Adjuster asks for purchase prices; insured replies that these follow "for the main items".D7 p.1–3

Amounts

ItemClaimedDocumentedStatusRemark
Sprinkler repair (coupling, pipe section)8,9008,900CheckQuote only, no invoice [D3 p.3]. May fall under the corrosion exclusion [D6 s.5.2].
Drying and cleaning46,30044,200CheckIncludes 2,100 for "preventive inspection of other sections" [D4 p.2], which reads as maintenance.
Stock damage318,400–OpenSales prices instead of purchase prices [D5 p.1] [D6 s.3.4].
Floor coating (building)39,000–No documentOnly mentioned in the notice of loss [D1 p.2]. The building belongs to [COMPANY_2].
Total412,60053,100Before deductible of 10,000 [D6 schedule].

"Documented" means: an amount stated in an invoice or quote among the documents. It is not a valuation of the loss.

Coverage check against the policy extract

Policy pointWhat the documents showAssessment
Insured peril: sprinkler leakage [D6 s.2.3]Sudden failure of a coupling with escape of water is described consistently in D1, D2 and D3.Supported
Exclusion: wear, corrosion [D6 s.5.2]Wording: "the cost of repairing or replacing any part that has failed due to … corrosion". The contractor names corrosion as cause [D3 p.2]. By its wording the exclusion concerns the coupling itself (8,900), not the water damage.Check
Condition: annual sprinkler inspection [D6 s.6.1]No inspection certificate among the documents. Consequences of a breach depend on the policy and the applicable law.Open
Basis of settlement for stock [D6 s.3.4]Purchase price at the time of loss. The list uses sales prices.Open
Business interruptionThe insured mentions three days of downtime [D1 p.2]. The policy extract contains no business interruption section.Cannot check

The coverage points are a reading of the policy text provided. They are not a legal opinion. Interpretation can depend on the full policy, the applicable law and case law.

Check points

  1. Valve closing time: 07:30 in the notice of loss [D1 p.1], 07:55 in the contractor's log [D3 p.1].
  2. Four and a half hours between alarm and discovery: relevant for the extent of the damage and possibly for the duty to limit the loss.
  3. Stock list: 41 items carry a delivery date after 14 September 2026 [D5 p.3–4], which would place them in the warehouse only after the loss.
  4. Building damage: the floor belongs to the building owner [D2 p.1]. It is unclear whether this item is claimed here or under the owner's policy.

Open questions and documents to request

  1. Inspection certificate of the sprinkler system for 2025 and 2026.
  2. Alarm transmission: was the alarm forwarded to a monitoring service, and when?
  3. Stock list with purchase prices and delivery notes for the 41 items dated after the loss.
  4. Final invoice for the sprinkler repair.
  5. Quote for the floor coating and confirmation who claims it.

Documents used

No.DocumentDatePages
D1First notice of loss, e-mail from [COMPANY_1]15 Sep 20262
D2Site visit note, loss adjuster [COMPANY_3]18 Sep 20264
D3Sprinkler contractor report with alarm log and quote, [COMPANY_4]22 Sep 20263
D4Invoice drying and cleaning6 Oct 20262
D5Stock damage list (Excel printed to PDF)9 Oct 20265
D6Policy extract: schedule and wording sections 1 to 6–12
D7E-mail thread insured and adjuster on stock prices10–14 Oct 20263
This report was prepared with AI from anonymised documents and checked by a CAPCON consultant. Every statement refers to its source. What is not in the documents is not in the report. Placeholders such as [COMPANY_1] are replaced with the real names on the client's own computer with the Local Anonymiser. Capacity Consulting AS · www.capcon.no · info@capcon.no